EV100F+BAC
Valve
Pattern
2-way
V'nom [l/s]
20
Flow rate adjustable
30...100% of V'nom
Fluid
Cold and warm water, water with glycol up to max. 50% vol.
Fluid temperature
-10...120°C [14...248°F]
Close-off pressure
690 kPa
Differential pressure Δpmax
340 kPa
Flow characteristic
Equal percentage
Leakage rate
Air-bubble tight, leakage rate A
Pipe connection
Flange
Actuator
Voltage AC/DC
AC/DC 24 V
Power consumption (running)
7 W
Power consumption (holding)
5 W
Power Consumption For Wire Sizing
11 VA
Connection Supply Control
Cable 1 m, 6x 0.75 mm²
Connection Ethernet
RJ45 socket
Control type
BACnet/IP
BACnet MS/TP
Modbus TCP
Modbus RTU
MP-Bus
DC 2...10 V
DC 0.5...10 V
Hybrid (communicative / analogue)
Cloud
Protection category
IP40