EV050R2+BAC
Electr. 2-way PI-CCV Belimo Energy Valve™, AC/DC 24 V, BACnet/IP, BACnet MS/TP, Modbus TCP, Modbus RTU, MP-Bus, Cloud, 2...10 V, DN 50, Internal and external thread, Rp 2"G 2 1/2", PN 25, ps 1600 kPa, V'nom 4.17 l/s, Fluid temperature -10...120°C [14...248°F], Glycol monitoring
Here are the specifications for the valve:
- Pattern: 2-way
- Nominal Flow Rate (V'nom): 4.17 l/s
- Flow Rate Adjustable: 25...100% of V'nom
- Fluid: Cold and warm water, water with glycol up to max. 60% vol.
- Fluid Temperature: -10...120°C [14...248°F]
- Close-off Pressure: 1400 kPa
- Differential Pressure (Δpmax): 350 kPa
- Differential Pressure Note: 200 kPa for low-noise operation
- Flow Characteristic: Equal percentage
- Leakage Rate: Air-bubble tight, leakage rate A
- Pipe Connection: Internal and external thread
Here are the specifications for the actuator:
- Voltage AC/DC: AC/DC 24 V
- Power Consumption (Running): 5 W
- Power Consumption (Holding): 3.9 W
- Power Consumption for Wire Sizing: 7.5 VA
- Connection Supply Control: Cable 1 m, 6x 0.75 mm²
- Connection Ethernet: RJ45 socket
-
Control Type:
- BACnet/IP
- BACnet MS/TP
- Modbus TCP
- Modbus RTU
- MP-Bus
- DC 2...10 V
- DC 0.5...10 V
- Hybrid (communicative / analogue)
- Cloud
- Protection Category: IP54